Barndominium Deck Post Height Calculator: Tallest Wood Post by Size and Load (Tyler, TX)

Under the 2021 IRC, a wood post under a single-level deck can only be so tall, and Table R507.4 sets that limit by post size, wood species and the deck area the post carries. At 90 sq ft per post under a 40 psf live load in southern pine, a 4 x 4 may stand up to 8 ft 10 in and a 4 x 6 up to 11 ft 4 in, measured from the underside of the beam to the top of the footing. The table stops at 14 ft and does not allow extrapolation.

In short

  • A barndominium deck post height calculator gives the tallest wood post allowed under a single-level deck, by size, species and load, from IRC 2021 Table R507.4.
  • At 90 sq ft per post and a 40 psf live load in southern pine: a 4 x 4 up to 8 ft 10 in, a 4 x 6 up to 11 ft 4 in.
  • The table tops out at 14 ft and does not allow extrapolation past 160 sq ft per post.
  • Example: a 9 ft post carrying 90 sq ft needs at least a 4 x 6 in southern pine.
On this page
  1. How the post check works
  2. Tallest southern pine post at 40 psf live load (IRC 2021 Table R507.4)
  3. Where deck post plans go wrong
  4. What to ask your builder
  5. Next step: get a written quote
  6. Sources
  7. Frequently asked questions

This barndominium deck post height calculator is for Tyler and Smith County owners planning a deck or porch on posts. Pick the load and the wood, then give the deck area one post holds and the post height. It shows the tallest 4 x 4, 4 x 6, 6 x 6 and 8 x 8 the code table allows and the smallest one that reaches your height. It pairs with our deck beam span calculator, the deck joist span calculator, the post footing size calculator and the deck ledger bolt spacing calculator. Local rules are in the Smith County permits guide.

En español: calculadora de altura de postes de terraza

1. The deck and the post

The first option is the usual case in East Texas, where snow loads are small. Pick it unless the plan or the building official names a ground snow load. Snow is not added to live load in the table.

Southern pine is the usual treated post in East Texas. The second option covers Douglas fir, hem-fir and spruce-pine-fir (incising factor included in the table). The third covers redwood, western cedars, ponderosa pine and red pine (incising factor not included). Posts are No. 2 grade.

Post spacing along the beam times the distance from the beam to the middle of the joists it holds. Posts 12 ft apart under 15 ft joists on an outer beam: 12 x 7.5 = 90. The 90 here is an example. The table covers up to 160.

Measured from the underside of the beam to the top of the footing or pier. The 9 here is an example.

4 x 4 post, 100 sq ft8 ft 4 insouthern pine, 40 psf, tallest
4 x 6 post, 100 sq ft10 ft 8 insouthern pine, 40 psf, tallest
6 x 6 post, 100 sq ft14 ftsouthern pine, 40 psf, tallest
Table height limit14 fttable stops there

Example: a 9 ft post under a deck that puts 90 sq ft on it, southern pine, 40 psf live load. The table allows 8 ft 10 in for a 4 x 4 and 11 ft 4 in for a 4 x 6, so a 4 x 6 is the smallest that fits (an example, not a ruling for any building).

How the post check works

  1. Pick the load.

    The first choice, 40 psf live load, is the usual case here. The example uses it.

  2. Pick the wood.

    Southern pine is the usual treated post. The example uses it.

  3. Find the area one post carries.

    Post spacing times the distance to the middle of the joist span. The example is 90 sq ft.

  4. Enter the post height.

    From the underside of the beam to the top of the footing. The example is 9 ft.

  5. Take it to the plan.

    Ask the builder to write the post size, wood and height on the deck detail.

Tallest southern pine post at 40 psf live load (IRC 2021 Table R507.4)

Area per post (sq ft)4 x 44 x 6
2014 ft14 ft
4013 ft 8 in14 ft
6011 ft13 ft 11 in
809 ft 5 in12 ft
1008 ft 4 in10 ft 8 in
1207 ft 5 in9 ft 8 in
1406 ft 9 in8 ft 10 in
1606 ft 2 in8 ft 2 in

Heights from the underside of the beam to the top of the footing. A southern pine 6 x 6 or 8 x 8 reaches 14 ft at every area on this line. Interpolation is allowed between areas; extrapolation is not.

Where deck post plans go wrong

  • Tall posts on a 4 x 4. The allowed height drops as the area per post grows. Check the real area, not the smallest column.
  • Posts that float in clay. R507.4.1 asks for connectors or 12 in of embedment; expansive soil cannot be counted on for side support.
  • Notches that eat the post. A notched post must still be sized for the beam it carries (R507.5.2).
  • A second level on a one-level table. Table R507.4 is for single-level decks only.
  • Height taken from the ground. The table measures to the top of the footing or pier, which can be below grade.

What to ask your builder

  • What post size and wood does the deck plan show? Ask for it on the deck detail, with the post height.
  • How much deck does each post carry? Ask for the post spacing and the joist span so you can check the area.
  • How are the posts held at the bottom? Ask whether the plan uses connectors or embedment, and what the soil report says.
  • How tall is the tallest post? A sloped lot makes some posts much taller than the rest.
  • Who is licensed? Read how to choose a barndominium builder.

Next step: get a written quote

This tool finds code items to ask about, not a design or a price. We are a referral service, not a contractor; we connect visitors with independent local providers. Use the form below to ask independent barndominium builders near Tyler for a written quote that states the deck post size, wood and height, and read how to choose a barndominium builder first.

Sources

Frequently asked questions

How tall can a 4x4 deck post be?

It depends on the load, the species and the deck area the post carries. In Table R507.4 of the 2021 IRC, a southern pine 4 x 4 under a 40 psf live load can be 14 ft tall when it carries 20 sq ft, and falls to 6 ft 2 in when it carries 160 sq ft. Height is measured from the underside of the beam to the top of the footing.

What size posts do I need for a tall deck?

A 6 x 6 or 8 x 8 southern pine post reaches the table's 14 ft limit at nearly every area and load in the table, while 4 x 4 and 4 x 6 posts lose allowed height as the area per post grows. A deck whose posts must be taller than 14 ft is outside the table and needs a design.

How do I find the deck area one post carries?

Multiply the distance between posts along the beam by the distance from the beam to the middle of the joist span it holds. For a beam at the outer edge with no cantilever, that is post spacing times half the joist span: posts 12 ft apart under 15 ft joists carry 12 x 7.5 = 90 sq ft. Table R507.4 calls this the tributary area.

Do deck posts have to be anchored to the footing?

Section R507.4.1 asks for lateral restraint, either manufactured connectors or at least 12 in of post embedment in surrounding soil or concrete piers. Where soils are expansive, compressible or shifting, which includes some East Texas clay, the surrounding soil is not to be relied on for lateral support.

Does the table apply to a two-level deck?

No. Section R507.4 says Table R507.4 is for single-level decks. A second level, a roof over the deck or a heavy hot tub needs a design from a professional or the building official.