In short
- A barndominium wall header size calculator answers one framing question: how big a beam must sit over a window or door in a wood-framed exterior bearing wall (IRC 2021 Table R602.7(1)).
- The table depends on three things: the load above (roof only, or floors too), the building width (12, 24 or 36 ft) and the opening width. This tool uses the 30 psf ground snow column, which the table footnote allows for lower snow loads.
- Example: a 6 ft opening in a 28 ft wide building under roof and ceiling needs two 2x10s (up to 6 ft 5 in) and 2 jack studs at each end.
- A steel or post-frame building has its openings designed by the manufacturer or an engineer; this table is for wood-framed walls.
On this page
- How the header check works
- Two-board header spans, roof and ceiling only (IRC 2021 Table R602.7(1))
- What the load above changes (two 2x10s, 24 ft wide building)
- What the number of boards changes (2x10, 24 ft wide, roof and ceiling)
- Where header sizing goes wrong
- What to ask your builder
- Next step: get a written quote
- Sources
- Frequently asked questions
This barndominium wall header size calculator is for Tyler and Smith County owners framing a living space, shop office or porch wall with 2x lumber who want to know what header to ask the builder for over each window and door. Enter the load above, the building width and the opening width; it names the smallest header in the code table that works and the jack studs under each end. It sits beside our windows and doors bid guide and our shop door size calculator.
En español: calculadora de tamaño de cabezal de ventana y puerta
Headers sit on studs: check the wall itself with our wall stud spacing calculator, which gives the widest stud spacing and tallest wall for 2x4 and 2x6 framing.
Your opening
Every size with this many boards
| Header | Longest span | Jack studs | Fits? |
|---|
Same header at each table width
| Building width | Longest span | Jack studs |
|---|
Example: roof and ceiling only, 28 ft wide building, 6 ft opening, two boards, top braced.
How the header check works
- Pick the load above the wall.
Roof and ceiling only is the usual one-story case. A floor above adds load, and the table is split into five rows. Example: roof and ceiling only.
- Enter the building width.
The table gives 12, 24 and 36 ft columns. A 28 ft building falls between the 24 and 36 ft columns, so we interpolate: two 2x10s allow 6 ft 10 in at 24 ft and 5 ft 9 in at 36 ft, which gives 6 ft 5 in at 28 ft.
- Enter the opening and the header build.
Your opening is rounded up to a whole inch. A 6 ft opening is 72 in against 77 in allowed, so 0 ft 5 in is spare.
- Read the smallest size that passes.
We list the boards in order from the smallest section up and show the first that fits. In our example two 2x8s allow only 5 ft 5 in, so they fail and two 2x10s pass.
- Count the jack studs.
The table lists how many jack studs carry each end. Between two table widths we use the larger number. If it says one, a framing anchor may replace the stud.
Two-board header spans, roof and ceiling only (IRC 2021 Table R602.7(1))
| Size | 12 ft | 24 ft | 36 ft |
|---|---|---|---|
| 2-2x4 | 4-0 | 3-1 | 2-7 |
| 2-2x6 | 6-0 | 4-7 | 3-10 |
| 2-2x8 | 7-7 | 5-9 | 4-10 |
| 2-2x10 | 9-0 | 6-10 | 5-9 |
| 2-2x12 | 10-7 | 8-1 | 6-10 |
Longest span in feet-inches (6-10 is 6 ft 10 in), by building width, at 30 psf ground snow load, No. 2 grade lumber. Headers are two boards of the size shown, on edge.
What the load above changes (two 2x10s, 24 ft wide building)
| Load carried | Longest span | Jack studs |
|---|---|---|
| Roof and ceiling | 6 ft 10 in | 2 |
| + 1 center-bearing floor | 5 ft 8 in | 2 |
| + 1 clear-span floor | 5 ft | 2 |
| + 2 center-bearing floors | 4 ft 9 in | 2 |
| + 2 clear-span floors | 3 ft 10 in | 2 |
Each floor above takes a large bite out of the span. The same two 2x10s that span 6 ft 10 in under a roof alone span only 3 ft 10 in to 4 ft 9 in with two floors above.
What the number of boards changes (2x10, 24 ft wide, roof and ceiling)
| Header | Longest span | Jack studs |
|---|---|---|
| two 10s | 6 ft 10 in | 2 |
| three 10s | 8 ft 7 in | 1 |
| four 10s | 9 ft 11 in | 1 |
More boards carry more, but also make the header thicker than a 2x4 wall (3 1/2 in deep), so a 2x6 wall is usually where three boards are used.
Where header sizing goes wrong
- Copying a header from another opening. A 3 ft window and a 12 ft door are not the same beam. Size each opening on its own.
- Forgetting the floor above. A loft or second story changes the row of the table. The same two 2x10s lose from about a sixth to nearly half of their span.
- Letting cripples bear on the header. The table assumes the top is braced. If short studs sit on it, 2x8 and larger spans drop to 70 percent.
- Skipping the jack studs. The span is only half the check: the studs under each end have to carry the load down to the floor.
- Using a stick-frame table on a steel building. Pre-engineered steel openings are designed by the manufacturer; do not substitute a wood header for a framed opening.
What to ask your builder
- What header is over each opening, and how many jack studs? Ask for the sizes in writing next to the window and door list.
- What load is on the wall? Roof only, or a loft above? Ask who checked the table row.
- Who designs the steel framed openings? In a steel shell, the metal building maker does. See the windows and doors bid guide.
- Is any header an engineered beam? Wide openings such as a 16 ft shop door are usually an LVL, steel or an engineer's design, not this table.
Next step: get a written quote
This tool checks one header against a code table, not the whole wall and not the price. We are a referral service, not a contractor; we connect visitors with independent local providers. Use the form below to ask independent barndominium builders near Tyler for a written quote that lists the header and jack studs at every opening, and read how to choose a barndominium builder first.
Sources
- 2021 International Residential Code, Chapter 6 (Texas edition on UpCodes): Table R602.7(1), girder and header spans for exterior bearing walls (Douglas fir-larch, hem-fir, Southern pine and spruce-pine-fir, No. 2 grade), with its footnotes on building width, jack studs, the 30 psf snow load rule and the 0.70 factor for headers not braced at the top.
- Whether the 2021 IRC applies to your lot depends on the city or lender; see our Smith County barndominium permits guide.
Frequently asked questions
What size header do I need over a 6 ft window or door?
It depends on the load above it and the building width. With only roof and ceiling above and a 24 ft wide building, the IRC 2021 table (R602.7(1), 30 psf snow column) allows 6 ft 10 in from two 2x10s, 8 ft 1 in from two 2x12s and 7 ft 3 in from three 2x8s. A 36 ft wide building or a floor above shrinks those spans. The calculator reads the exact figure for your inputs.
What is a jack stud and how many do I need?
A jack stud (also called a trimmer) is the short stud under each end of the header that carries its load down to the sill or plate. The table gives the number needed at each end, usually one or two, and sometimes three or four on wide spans with floors above. Where the table says one, an approved framing anchor can stand in for the jack stud.
Does this apply to a steel-frame or post-frame barndominium?
Not directly. The table is for wood-framed exterior bearing walls. In a pre-engineered steel building the manufacturer designs the framed openings for the loads in the order, and a post-frame (pole) building has an engineered design for its openings. Ask who sealed that design. The calculator is most useful for stick-framed walls, such as a living space framed inside a steel shell.
Why is the header sized by the building width?
The roof sends load to the walls from half the building width on each side, so a wider building puts more load on every header. The table lists 12, 24 and 36 ft widths and allows interpolation between them. This calculator interpolates and rounds the span down to a whole inch.
Does a header need to be braced at the top?
The table assumes the top of the header is braced by perpendicular framing. If cripple studs bear on the header instead, the table says the 2x8, 2x10 and 2x12 spans must be multiplied by 0.70 or the header designed. The calculator has a switch for it.
Does the calculator give a price?
No. It gives sizes and spans only, with no prices. Ask for written quotes that name the header size and the number of jack studs for each opening.