In short
- This barndominium generator size calculator adds up the loads you want on during an outage and returns a low and high generator size in kW.
- Two numbers matter: running watts (everything on at once) and the start surge of the biggest motor, usually the central A/C compressor.
- Example: 3-ton A/C, two refrigerators, a 1 hp well pump and a 1,500 W allowance comes to about 11 to 13 kW.
- A soft-start kit on the A/C is the cheapest lever on size: the same house drops to 9 to 10.5 kW.
On this page
This barndominium generator size calculator is for East Texas owners planning backup power for storm outages who want to know what kW to ask an electrician or dealer for. Pick the loads you want running at once (central A/C, refrigerators, well pump, electric water heater) and it adds their running watts, finds the single biggest start surge, and shows a low and high generator size. It sits beside our electrical service size calculator, our HVAC size calculator, our water heater size calculator and our septic and well guide.
En español: calculadora de tamaño de generador para barndominium
| Load | Running W | Start surge W |
|---|
Same house, other A/C start type (kW)
| A/C start | Low kW | High kW |
|---|
Same loads, other A/C sizes (kW)
| A/C size | Low kW | High kW |
|---|
Example: a 3-ton A/C with a standard start, two refrigerators, a 1 hp well pump, gas water heating and the 1,500 W allowance.
How the generator size is worked out
- Add running watts.
Central A/C 1,200 W per ton, 200 W per refrigerator, the well pump by horsepower, 4,500 W for an electric tank water heater and 1,500 W for lights and plugs. Example: 3,600 + 400 + 1,400 + 1,500 = 6,900 W.
- Find the biggest start surge.
Motors draw extra for a moment when they start. Extra for each: A/C 1,300 W per ton (3,900 W for 3 tons), well pump 1,600 W, refrigerator 800 W. Take the largest: 3,900 W.
- Build the low end.
Running plus the biggest surge: 6,900 + 3,900 = 10,800 W, rounded up to the next half kW: 11 kW.
- Build the high end.
Running x 1.25 plus the surge: 8,625 + 3,900 = 12,525 W, rounded up: 13 kW. The 25% cushion is our planning assumption.
- Convert to amps.
kW x 1,000 / 240 V: 13 kW is 55 A; 11 kW is 46 A. This is the load on the generator breaker, not the size of your service.
Planning values this tool uses
| Load | Running W | Start W |
|---|---|---|
| A/C per ton, standard start | 1,200 | 2,500 |
| A/C per ton, soft start | 1,200 | 1,800 |
| Refrigerator or freezer | 200 | 1,000 |
| Well pump 1/2 hp | 1,000 | 2,100 |
| Well pump 1 hp | 1,400 | 3,000 |
| Well pump 1.5 hp | 1,800 | 4,000 |
| Electric tank water heater | 4,500 | none |
| Lights and plugs allowance | 1,500 | none |
These are our planning midpoints. Published charts disagree: 3-ton A/C running watts run from about 3,500 to 4,000, start watts from about 5,000 (soft start) to 9,000, and a 1 hp well pump from about 750 to 2,000 running. Use the nameplate where you can.
A/C size against generator size (two refrigerators, 1 hp well pump, standard start)
| A/C size | Low kW | High kW |
|---|---|---|
| 2 tons | 8.5 | 10 |
| 3 tons | 11 | 13 |
| 4 tons | 13.5 | 15.5 |
| 5 tons | 16 | 18.5 |
Each added ton of A/C adds about 1,500 W to the low end because of its running load and 1,300 W to the start surge.
Where generator plans go wrong
- Sizing to running watts only. The A/C compressor can pull about double its running watts for a moment. A generator that cannot ride that out trips or stalls.
- Forgetting the electric water heater. At 4,500 W it can add more than the A/C. Many owners leave it off during an outage; decide before you size.
- Trusting chart numbers for your A/C. Two 3-ton units can differ a lot. Ask for the running and locked-rotor amps on the nameplate.
- Running a portable unit near the house. Generators put out carbon monoxide. Run portables outdoors and well away from windows, doors and vents.
- Skipping the transfer switch. A permanent connection needs listed transfer equipment so power cannot back-feed the utility line. A plug into a dryer outlet is not that.
What to ask your electrician and dealer
- What are the running and locked-rotor amps on my A/C and well pump? Get the numbers from the nameplates and plug them in; they beat any chart.
- Does the A/C have a soft-start kit, or can one be added? This is the cheapest way to shrink the generator. Also see our HVAC size calculator.
- What is the generator rated at on propane or natural gas? Ratings on gas can be lower than on gasoline. Ask for the number on your fuel.
- What transfer switch or interlock goes with it, and who pulls the permit? See our Smith County permits guide and our electrical service size calculator.
- Where does the unit sit and how far from openings? Get the manufacturer clearances in writing before the pad or the fuel line goes in.
Next step: get a written quote
This tool estimates a size, not a design and not a price. We are a referral service, not a contractor; we connect visitors with independent local providers. Use the form below to ask independent barndominium builders near Tyler for a written quote that names the generator or the transfer switch rough-in, and read how to choose a barndominium builder first.
Sources
- Champion Power Equipment: What Size Generator Do I Need?: running versus starting watts, sizing steps, typical refrigerator and central A/C ranges.
- Virginia Cooperative Extension: Estimating Appliance and Home Electronic Energy Use: appliance wattage ranges.
- U.S. Consumer Product Safety Commission: Generators and Engine-Driven Tools: use outdoors, away from windows, doors and vents.
- EC&M: NEC Requirements for Emergency and Standby Systems: Article 702 and transfer equipment. Section numbers differ by NEC edition; confirm the edition your building official has adopted.
- The watt values are our planning midpoints of published ranges, and the 25% cushion is our assumption. This is not a load calculation under the NEC. See our electric service guide for Smith County for who connects power.
Frequently asked questions
What size generator do I need for a barndominium?
Add the running watts of everything you want on at once, then add the biggest single start surge. For a 3-ton A/C, two refrigerators, a 1 hp well pump and a 1,500 W allowance for lights and plugs the tool gives about 11 to 13 kW. Your nameplates change that, so enter your own loads and confirm with an electrician.
Why does the central A/C drive the size?
Its compressor draws a short burst, often about double its running watts, when it starts. The tool counts that burst once. A soft-start kit lowers it; in our example it drops the size from 11 to 13 kW to 9 to 10.5 kW.
Can a generator run the whole barndominium?
Possibly, but a whole-building generator is sized for every circuit, which is a different and larger calculation. This tool is for essentials. For service size see our electrical service size calculator.
Do I need a transfer switch?
For a generator wired to the building, yes: NEC Article 702 requires listed transfer or interconnection equipment so the generator and the utility cannot feed each other (section numbers differ by edition). Ask your electrician and the building official.
Where can I put a generator?
Portable generators run outdoors only, well away from windows, doors and vents, per the U.S. Consumer Product Safety Commission. A permanent unit follows the maker's clearance and your local permit.
Does the calculator give a price?
No. It gives watts, kW and amps only, with no prices. Ask for written quotes that name the generator size, the transfer equipment and who pulls the permit.