This barndominium shop subpanel wire size calculator takes the breaker size, the one-way distance and the metal (copper or aluminum) and shows the smallest feeder wire for current, the smallest for voltage drop, and the size to ask your electrician about. It shows no prices.
It is a planning check on a quote, not a design. The electrician sizes the feeder under the National Electrical Code edition your city or county has adopted. To see whether the whole property needs a bigger service first, use the electrical service size calculator.
En español: Calculadora de tamaño de cable para el subpanel del taller
| Line | Amount |
|---|
The math behind the number
- Wire for current
Pick the smallest size whose 75 C ampacity is at least the breaker. For a 100 A breaker that is 3 AWG copper (100 A) or 1 AWG aluminum (100 A).
- Voltage drop
Drop in volts = 2 x K x amps x one-way feet / circular mils, with K about 12.9 for copper and 21.2 for aluminum. Divide by 240 for percent.
- Demo: 100 A, 150 ft, aluminum
1 AWG (83,690 circular mils) drops about 7.6 V, or 3.2%: over the 3% target. 1/0 AWG (105,600) drops about 6.0 V, or 2.5%: it passes.
- Ask for the larger
The size to ask for is whichever is bigger: the current size or the voltage-drop size. The ground wire comes from Table 250.122 by breaker size.
Examples at the 3% target, planning arithmetic with the full breaker as the load.
| Case | Current | Drop | Ask for |
|---|---|---|---|
| 60 A, 100 ft, Al | 4 AWG | 4 AWG | 4 AWG |
| 100 A, 150 ft, Al | 1 AWG | 1/0 AWG | 1/0 AWG |
| 100 A, 300 ft, Cu | 3 AWG | 2/0 AWG | 2/0 AWG |
| 200 A, 200 ft, Al | 250 kcmil | 250 kcmil | 250 kcmil |
Distance changes everything: the same 100 A aluminum feeder needs 1 AWG at 40 ft but 1/0 AWG at 150 ft and more beyond that. Measure the trench route before you compare bids.
Reference: ampacity at 75 C
Allowable amps for 3 conductors in conduit at 30 C ambient from NEC Table 310.16, 75 C column, as widely published. Terminals on most panels are rated 75 C.
| Size | Copper (A) | Aluminum (A) |
|---|---|---|
| 8 AWG | 50 | 40 |
| 6 AWG | 65 | 50 |
| 4 AWG | 85 | 65 |
| 3 AWG | 100 | 75 |
| 2 AWG | 115 | 90 |
| 1 AWG | 130 | 100 |
| 1/0 AWG | 150 | 120 |
| 2/0 AWG | 175 | 135 |
| 3/0 AWG | 200 | 155 |
| 4/0 AWG | 230 | 180 |
| 250 kcmil | 255 | 205 |
| 300 kcmil | 285 | 230 |
| 350 kcmil | 310 | 250 |
| 400 kcmil | 335 | 270 |
| 500 kcmil | 380 | 310 |
What the code says about a shop feeder
- Ampacity. NEC Table 310.16 gives the allowable amps by wire size and insulation temperature. Equipment terminals limit you to the column they are rated for (NEC 110.14(C)); 75 C is common.
- Voltage drop. NEC 215.2 has an informational note recommending about 3% for a feeder and 5% for feeder plus branch circuit. It is a recommendation, not an enforceable rule.
- Detached building. NEC 250.32 covers grounding at a separate building. New feeders normally carry a separate equipment ground, and the neutral and ground stay apart in the shop panel.
- Equipment ground size. NEC Table 250.122 sets it from the feeder breaker; if the hot wires are increased for voltage drop, 250.122(B) asks for the ground to be increased in proportion.
- Burial. NEC Table 300.5 gives minimum cover. It is commonly summarized as 18 in for PVC conduit and 24 in for direct-burial cable, but depth depends on the wiring method, so ask the electrician.
Sources: NEC (NFPA 70) Table 310.16, 110.14(C), 215.2 informational note, 250.32, Table 250.122 and Table 300.5, as summarized by Mike Holt on Article 215 and published copies of Table 310.16; resistance values are the commonly used approximations for 75 C. Texas cities and counties adopt their own NEC edition and amendments.
Questions to ask the electrician
- Which wire size and metal are you quoting for the shop feeder, and what distance did you assume?
- Is the quote for four wires with a separate ground, and where does the shop disconnect go?
- Did you size for voltage drop, or only for the breaker?
- Is the conduit size and burial depth on the quote?
- Is there room on the main panel and the utility service for this feeder? See the electric service guide for Smith County.
What the result leaves out
| Item | Why it is separate |
|---|---|
| Conduit size and fill | Depends on wire count and size; the electrician sets it. |
| Panel spaces and main lugs | Set by the shop circuits, not the feeder. |
| Welder and compressor loads | Add them to the load calculation; see shop planning. |
| Permit and inspection | Ask the building official; see Smith County permits. |
Not electrical design: use this tool to understand a bid. Only a licensed electrician can size and install the feeder. A bid that does not name the wire size, metal and distance is not comparable to one that does.
How to use the result with electricians
- Get the numbers
Breaker size, one-way distance and the wire metal quoted.
- Run the calculator
Compare the size to ask for with each bid.
- Ask about gaps
If a bid is thinner, ask why. Use the form below to request quotes from independent local electricians and builders.
We are a referral service that connects you with independent local pros; we do not install wire or give quotes ourselves.
Frequently asked questions
What size wire do I need for a 100 amp subpanel in a shop?
It depends on the metal and the distance. At the 75 C column of NEC Table 310.16, a 100 A feeder needs 3 AWG copper or 1 AWG aluminum for current alone. Over a long run, voltage drop usually pushes the wire up one or two sizes. Use the calculator with your own distance and ask the electrician to confirm.
Does voltage drop change the wire size?
Yes, on long runs. The NEC only recommends keeping feeder drop to about 3% (and about 5% for feeder plus branch circuit together) in an informational note, so it is not a pass or fail rule, but motors, welders and compressors run poorly on sagging voltage. A 100 A feeder over 150 ft of aluminum loses about 3.2% on 1 AWG and about 2.5% on 1/0 AWG.
Can I use aluminum wire for a shop feeder?
Yes, aluminum feeder wire is common and allowed when the terminals are rated for it. It needs a larger size than copper for the same current, and the lugs must be listed for aluminum and torqued to spec. The electrician decides; this page only shows both.
How many wires go to a detached shop panel?
Normally four: two hots, an insulated neutral and a separate equipment ground, with the neutral and ground kept apart in the shop panel (NEC 250.32). Older shops sometimes had three wires; new work generally does not. Ask the electrician what your adopted code edition requires.
Does this calculator tell me the size of the shop panel or the service?
No. It sizes the wire between two panels from a breaker you choose. Whether the property needs a bigger service, how many spaces the shop panel needs and where the disconnect goes are separate questions for the electrician and the utility.